# ESPHome modbus - heatpump Gree Versati III ## Description: This manual describes how to connect the device to Home Assistant via Modbus protocol using ESP and RS485/TTL converter. In this case it is about connecting a Gree Versati III 10kw heat pump. ## Info: -use only shielded cable, otherwise the error "Modbus CRC Check Failed!" may appear in the log. -put a 120 ohm resistor after the last connected device -modbus datasheet: [Gree Versati III]([https://www.laskakit.cz/prevodnik-ttl-na-rs-485--max485/](https://github.com/peca2345/ESPHome-modbus-heatpump-Gree-Versati-III/blob/main/modbus-versati-iii-en.pdf)) ## Components: - ESP8266 / ESP32 - RS485/TTL converter: [SHOP](https://www.laskakit.cz/prevodnik-ttl-na-rs-485--max485/) ## Schematic: ![Schema](https://github.com/peca2345/ESPHome-modbus-heatpump-Gree-Versati-III/blob/main/IMG/schematic.png?raw=true) ## ESPHome code: ``` uart: id: mod_bus tx_pin: GPIO16 rx_pin: GPIO17 baud_rate: 9600 stop_bits: 2 modbus: flow_control_pin: GPIO23 send_wait_time: 100ms id: modbus_versati3 modbus_controller: - id: versati3 ## the Modbus device addr address: 0x1 modbus_id: modbus_versati3 setup_priority: -10 update_interval: 15s number: - platform: modbus_controller modbus_controller_id: versati3 name: "nasi_komora_modbus_tank_target_temp_set" address: 13 unit_of_measurement: "°C" value_type: S_WORD entity_category: config sensor: - platform: modbus_controller modbus_controller_id: versati3 name: "nasi_komora_modbus_tank_target_temp" address: 13 unit_of_measurement: "°C" register_type: holding value_type: U_WORD accuracy_decimals: 1 # filters: # - multiply: 0.1 ```