-**restore_mode** (*Optional*): See :ref:`Switch <config-switch>`, since this configuration variable is inherited. The default value for this setting is ``DISABLED`` (recommended).
``DISABLED`` leaves the initial state up to the hardware: usually the state lives in the device and ESPHome does not need to remember it. The switch frontend will show an undetermined
state until the real state is retrieved from the device on the next refresh. Use any other setting if a reboot of your ESPHome device is tied to a reboot of the modbus device.
offset from start address in bytes. If more than one register is read a modbus read registers command this value is used to find the start of this datapoint relative to start address. The component calculates the size of the range based on offset and size of the value type
The value for offset depends on the register type. For holding input registers the offset is in bytes. For coil and discrete input resisters the LSB of the first data byte contains the coil addressed in the request. The other coils follow toward the high-order end of this byte and from low order to high order in subsequent bytes. For the registers offset is the position of the relevant bit.
To get the value of the coil register 2 can be retrieved using address: 2 / offset: 0 or address: 0 / offset 2
-**bitmask** (*Optional*, int): Some values are packed in a response. The bitmask is used to determined if the result is true or false.
-**skip_updates** (*Optional*, int): By default all sensors of a modbus_controller are updated together. For data points that don't change very frequently updates can be skipped. A value of 5 would only update this sensor range in every 5th update cycle
-**use_write_multiple** (*Optional*, boolean): By default the modbus command ``Force Single Coil`` (function code 5) is used to send state changes to the device. If your device only supports ``Force Multiple Coils`` (function code 15) set this option to true.
-**custom_command** (*Optional*, list of bytes): raw bytes for modbus command. This allows using non-standard commands. If ``custom_command`` is used ``address`` and ``register_type`` can't be used.
-**x** (float): The float value to be sent to the modbus device
-**payload** (``std::vector<uint8_t>&payload``): empty vector for the payload. If payload is set in the lambda it is sent as a custom command and must include all required bytes for a modbus request
*note:* because the response contains data for all registers in the same range you have to use ``data[item->offset]`` to get the first response byte for your sensor.
-**item** (const pointer to a Switch derived object): The sensor object itself.
For holding registers the write command will be write_single_register. Because the offset for holding registers is given in bytes and the size of a register is 16 bytes the start_address is calculated as ``start_address + offset/2``