Thermostat enhancements 2 doc update (#1360)
This commit is contained in:
parent
bf962b22d0
commit
45c8788d02
|
@ -139,6 +139,7 @@ Examples:
|
|||
Got all that? Great. Let's take a closer look at some configuration.
|
||||
|
||||
Configuration Variables:
|
||||
------------------------
|
||||
|
||||
The thermostat controller uses the sensor to determine whether it should heat or cool.
|
||||
|
||||
|
@ -182,15 +183,24 @@ These are triggered when the climate control **action** is changed by the thermo
|
|||
the climate device should enter its idle state (not cooling, not heating).
|
||||
- **heat_action** (*Optional*, :ref:`Action <config-action>`): The action to call when
|
||||
the climate device should enter heating mode to increase the current temperature.
|
||||
- **supplemental_heating_action** (*Optional*, :ref:`Action <config-action>`): The action
|
||||
to call when the climate device should activate supplemental heating to (more aggressively)
|
||||
increase the current temperature. *This action is called repeatedly at an interval defined by*
|
||||
``max_heating_run_time`` *(see below).*
|
||||
- **cool_action** (*Optional*, :ref:`Action <config-action>`): The action to call when
|
||||
the climate device should enter cooling mode to decrease the current temperature.
|
||||
- **supplemental_cooling_action** (*Optional*, :ref:`Action <config-action>`): The action
|
||||
to call when the climate device should activate supplemental cooling to (more aggressively)
|
||||
decrease the current temperature. *This action is called repeatedly at an interval defined by*
|
||||
``max_cooling_run_time`` *(see below).*
|
||||
- **dry_action** (*Optional*, :ref:`Action <config-action>`): The action to call when
|
||||
the climate device should perform its drying (dehumidification) action. The thermostat
|
||||
controller does not trigger this action; it is invoked by ``dry_mode`` (see below).
|
||||
- **fan_only_action** (*Optional*, :ref:`Action <config-action>`): The action to call when
|
||||
the climate device should activate its fan only (but does not heat or cool). The thermostat
|
||||
controller triggers this action based on the upper target temperature when set to
|
||||
``fan_only_mode`` (see below).
|
||||
the climate device should activate its fan only (but does not heat or cool). When ``fan_only_cooling``
|
||||
is set to ``false``, the thermostat controller immediately triggers this action when set to
|
||||
``fan_only_mode``; however, when ``fan_only_cooling`` is set to ``true``, this action is called
|
||||
based on the upper target temperature (similar to ``cool_action`` above).
|
||||
- All other options from :ref:`Climate <config-climate>`.
|
||||
|
||||
**At least one of** ``cool_action``, ``fan_only_action``, ``heat_action``, **and** ``dry_action``
|
||||
|
@ -266,13 +276,20 @@ These should be used to control the fan only, if available.
|
|||
- **swing_both_action** (*Optional*, :ref:`Action <config-action>`): The action to call when the fan
|
||||
should oscillate in horizontal and vertical directions.
|
||||
|
||||
Advanced Options
|
||||
****************
|
||||
Advanced Configuration/Behavior:
|
||||
--------------------------------
|
||||
|
||||
**Set Point Options/Behavior**
|
||||
Set Point Options/Behavior
|
||||
**************************
|
||||
|
||||
- **set_point_minimum_differential** (*Optional*, float): For dual-point/dual-function systems, the minimum
|
||||
required temperature difference between the heat and cool set points.
|
||||
required temperature difference between the heat and cool set points. Defaults to 0.5 °C.
|
||||
- **supplemental_cooling_delta** (*Required with* ``supplemental_cooling_action``, float): When the temperature
|
||||
difference between the upper set point and the current temperature exceeds this value,
|
||||
``supplemental_cooling_action`` will be called immediately.
|
||||
- **supplemental_heating_delta** (*Required with* ``supplemental_heating_action``, float): When the temperature
|
||||
difference between the lower set point and the current temperature exceeds this value,
|
||||
``supplemental_heating_action`` will be called immediately.
|
||||
- **away_config** (*Optional*): Additionally specify target temperature range settings for away mode.
|
||||
Away mode can be used to have a second set of target temperatures (for example, while the user is
|
||||
away or sleeping/at night).
|
||||
|
@ -285,17 +302,56 @@ Advanced Options
|
|||
**If configured, at least one of** ``default_target_temperature_low`` **and** ``default_target_temperature_high``
|
||||
**must be specified in the away mode configuration.**
|
||||
|
||||
**Additional Actions/Behavior**
|
||||
Additional Actions/Behavior
|
||||
***************************
|
||||
|
||||
- **target_temperature_change_action** (*Optional*, :ref:`Action <config-action>`): The action to call when the
|
||||
thermostat's target temperature(s) is/are changed.
|
||||
- **startup_delay** (*Optional*, boolean): If set to ``true``, when ESPHome starts, ``min_cooling_off_time``,
|
||||
``min_fanning_off_time``, and ``min_heating_off_time`` must elapse before each respective action may be invoked.
|
||||
This option provides a way to prevent damage to equipment (for example) disrupted by a power interruption.
|
||||
Defaults to ``false``.
|
||||
- **fan_only_action_uses_fan_mode_timer** (*Optional*, boolean): If set to ``true``, the ``fan_only_action`` will
|
||||
share the same delay timer used for all ``fan_mode`` actions. The minimum fan switching delay is then determined
|
||||
by ``min_fan_mode_switching_time`` (see below). This is useful when ``fan_only_action`` controls the same physical
|
||||
fan as the ``fan_mode`` actions, common in forced-air HVAC systems.
|
||||
- **fan_only_cooling** (*Optional*, boolean): If set to ``true``, when in the ``fan_only_mode`` climate mode,
|
||||
the ``fan_only_action`` will only be called when the observed temperature exceeds the upper set point plus
|
||||
``cool_deadband``. When set to ``false`` (the default), ``fan_only_action`` is called immediately when
|
||||
``fan_only_mode`` is activated, regardless of the current temperature or set points.
|
||||
- **target_temperature_change_action** (*Optional*, :ref:`Action <config-action>`): The action to call when the
|
||||
thermostat's target temperature(s) is/are changed.
|
||||
``fan_only_mode`` is activated, regardless of the current temperature or set points. Defaults to ``false``.
|
||||
- **fan_with_cooling** (*Optional*, boolean): If set to ``true``, ``fan_only_action`` will be called whenever
|
||||
``cool_action`` is called. This is useful for forced-air systems where the fan typically runs with cooling.
|
||||
Defaults to ``false``.
|
||||
- **fan_with_heating** (*Optional*, boolean): If set to ``true``, ``fan_only_action`` will be called whenever
|
||||
``heat_action`` is called. This is useful for forced-air systems where the fan typically runs with heating.
|
||||
Defaults to ``false``.
|
||||
- **max_cooling_run_time** (*Required with* ``supplemental_cooling_action``, :ref:`config-time`): Duration after
|
||||
which ``supplemental_cooling_action`` will be called when cooling is active. Note that
|
||||
``supplemental_cooling_action`` will be called repeatedly at an interval defined by this parameter, as well,
|
||||
enabling multiple stages of supplemental (auxiliary/emergency) cooling.
|
||||
- **max_heating_run_time** (*Required with* ``supplemental_heating_action``, :ref:`config-time`): Duration after
|
||||
which ``supplemental_heating_action`` will be called when heating is active. Note thermostat
|
||||
``supplemental_heating_action`` will be called repeatedly at an interval defined by this parameter, as well,
|
||||
enabling multiple stages of supplemental (auxiliary/emergency) heating.
|
||||
- **min_cooling_off_time** (*Required with* ``cool_action``, :ref:`config-time`): Minimum duration the cooling action
|
||||
must be disengaged before it may be engaged.
|
||||
- **min_cooling_run_time** (*Required with* ``cool_action``, :ref:`config-time`): Minimum duration the cooling action
|
||||
must be engaged before it may be disengaged.
|
||||
- **min_fanning_off_time** (*Required with* ``fan_only_action``, :ref:`config-time`): Minimum duration the fanning
|
||||
action must be disengaged before it may be engaged.
|
||||
- **min_fanning_run_time** (*Required with* ``fan_only_action``, :ref:`config-time`): Minimum duration the fanning
|
||||
action must be engaged before it may be disengaged.
|
||||
- **min_heating_off_time** (*Required with* ``heat_action``, :ref:`config-time`): Minimum duration the heating action
|
||||
must be disengaged before it may be engaged.
|
||||
- **min_heating_run_time** (*Required with* ``heat_action``, :ref:`config-time`): Minimum duration the heating action
|
||||
must be engaged before it may be disengaged.
|
||||
- **min_idle_time** (*Required*, :ref:`config-time`): Minimum duration the idle action must be active before calling
|
||||
another climate action.
|
||||
- **min_fan_mode_switching_time** (*Required with any* ``fan_mode`` *action*, :ref:`config-time`): Minimum duration
|
||||
any given fan mode must be active before it may be changed.
|
||||
|
||||
|
||||
**Hysteresis Values**
|
||||
Hysteresis Values
|
||||
*****************
|
||||
|
||||
- **cool_deadband** (*Optional*, float): The minimum temperature differential (temperature above the set point)
|
||||
before calling the cooling :ref:`action <config-action>`. Defaults to 0.5 °C.
|
||||
|
@ -305,11 +361,6 @@ Advanced Options
|
|||
before calling the heating :ref:`action <config-action>`. Defaults to 0.5 °C.
|
||||
- **heat_overrun** (*Optional*, float): The minimum temperature differential (heating beyond the set point)
|
||||
before calling the idle :ref:`action <config-action>`. Defaults to 0.5 °C.
|
||||
- **hysteresis** (*Optional*, float): This configuration option provides a one-line way to configure *all* "deadband"
|
||||
and "overrun" values identified above. Note that the above configuration options each take precedence over this
|
||||
value. *This option is deprecated and may be removed in a future release.*
|
||||
|
||||
|
||||
|
||||