@ -8,7 +8,14 @@ Bang Bang Climate Controller
|
||||
The ``bang_bang`` climate platform allows you to regulate a value with a
|
||||
`bang-bang controller <https://en.wikipedia.org/wiki/Bang%E2%80%93bang_control>`__ (also called hysteresis controller).
|
||||
|
||||
The operation principle of a bang_bang controller is quite simple. First, you specify an observable
|
||||
.. note::
|
||||
|
||||
A number of people have asked about the behavior of the bang-bang controller. In version 1.15, a
|
||||
:doc:`thermostat <thermostat>` component was added which behaves more like a common thermostat; it is
|
||||
essentially two bang-bang controllers in one. Please see the `Bang-bang vs. Thermostat`_ section below
|
||||
if you are not sure which is appropriate for your application.
|
||||
|
||||
The bang-bang controller's principle of operation is quite simple. First, you specify an observable
|
||||
value (for example the temperature of a room). The controller will try to keep this observed value
|
||||
in a defined range. To do this, the controller can activate objects like a heating unit to change
|
||||
the observed value.
|
||||
@ -57,8 +64,8 @@ Do note that the actions are only called when the current temperature leaves the
|
||||
idle_action:
|
||||
- switch.turn_off: heater
|
||||
|
||||
Configuration variables:
|
||||
------------------------
|
||||
Configuration variables
|
||||
-----------------------
|
||||
|
||||
- **sensor** (**Required**, :ref:`config-id`): The sensor that is used to measure the current temperature.
|
||||
- **default_target_temperature_low** (**Required**, float): The default low target temperature for
|
||||
@ -90,6 +97,87 @@ Advanced options:
|
||||
While this platform uses the term temperature everywhere, it can also be used for other values.
|
||||
For example, controlling humidity is also possible with this platform.
|
||||
|
||||
Bang-bang vs. Thermostat
|
||||
------------------------
|
||||
|
||||
The behavior of the bang-bang controller is a topic that has surfaced on the ESPHome Discord server
|
||||
countless times -- many people have been confused by what it does. While they are similar, there are
|
||||
two key differences between the bang-bang component and the :doc:`thermostat <thermostat>` component:
|
||||
|
||||
- When actions are triggered
|
||||
- How the set points are used by the controller
|
||||
|
||||
Now is a good time to ensure you understand exactly how a bang-bang controller should behave; if you do not have
|
||||
a clear understanding of this, be sure to check out the
|
||||
`Wikipedia article <https://en.wikipedia.org/wiki/Bang%E2%80%93bang_control>`__.
|
||||
|
||||
The Problem with Dual-Function Systems
|
||||
**************************************
|
||||
|
||||
If you are not attempting to operate a system that can both heat and cool, you'll likely want to skip to the next
|
||||
section about user interface.
|
||||
|
||||
As outlined above, in general:
|
||||
|
||||
- As soon as the temperature goes below the *lower* target temperature, ``heat_action`` is called to activate heating.
|
||||
- Heating will continue until the temperature reaches the *upper* target temperature, at which point ``idle_action`` is called to stop heating.
|
||||
- As soon as the temperature goes above the *upper* target temperature, ``cool_action`` is called to activate cooling.
|
||||
- Cooling will continue until the temperature reaches the *lower* target temperature, at which point ``idle_action`` is called to stop cooling.
|
||||
|
||||
A single bang-bang controller may work well for systems that only heat or only cool; however, it begins to break down
|
||||
when applied to systems that may both heat *and* cool. This is simply because both actions are tied to both set
|
||||
points -- that is, the point at which heating stops *is also the point at which cooling begins*. The reverse is also
|
||||
true: the point at which cooling stops *is also the point at which heating begins*. Let's look at an example:
|
||||
|
||||
Consider a system that both heats and cools. The ``target_temperature_low`` set point is 20 °C while the
|
||||
``target_temperature_high`` set point is 22 °C. The sensor reports that the temperature is 19.75 °C, so the controller
|
||||
calls ``heat_action`` to activate heating. Heating continues until the temperature reaches ``target_temperature_high``
|
||||
(22 °C in this case). Once this temperature is achieved, ``idle_action`` is called to stop heating. *However*, should
|
||||
temperature drift even slightly above ``target_temperature_high``--even just a fraction of a degree for a fraction of
|
||||
a second--the controller will call ``cool_action`` to begin cooling. Now, cooling will continue until
|
||||
``target_temperature_low`` is reached again, but, as before, should the temperature drift even slightly below
|
||||
``target_temperature_low`` for even a fraction of a second, ``heat_action`` will be invoked again, and the cycle will
|
||||
repeat. It will "ping-pong" between the two set points, potentially forever. Oscillation at the "edges" of the
|
||||
hysteresis window, or going past the set point in either direction, should be expected; consider, for example, a heater
|
||||
that is turned off after it reaches its set point. The heating element will remain hot (potentially for quite a while),
|
||||
and as such will continue to heat the air until the element fully cools down to match the ambient air/room temperature.
|
||||
|
||||
The :doc:`thermostat <thermostat>` component differs in that there is hysteresis around *each* set point. For example,
|
||||
if the ``target_temperature_low`` set point is 20 °C, and the (default) hysteresis value of 0.5 °C is used,
|
||||
``heat_action`` is called at a temperature of 19.5 °C and ``idle_action`` is called at 20.5 °C. If cooling, as defined
|
||||
by ``target_temperature_high``, is set to 22 °C, ``cool_action`` would be called at 22.5 °C and ``idle_action`` called
|
||||
at 21.5 °C. Again, it is essentially two bang-bang controllers in one.
|
||||
|
||||
Behavioral differences aside, there is another important difference between these two components: user interface.
|
||||
|
||||
User Interface
|
||||
**************
|
||||
|
||||
The interaction with this component via the Home Assistant user interface is also different than what is seen on most
|
||||
common residential thermostats. Generally speaking, most thermostats allow either one or two set points -- one of them
|
||||
is associated with heating while the other with cooling, and this is exactly how the :doc:`thermostat <thermostat>`
|
||||
component uses them. If you set the "heat" set point to 20 °C, most people assume this means the heating system will
|
||||
keep the temperature as close to 20 °C as possible. The same is true for the upper set point, for cooling: if you set
|
||||
a temperature of 22 °C, most people assume the cooling system will keep the temperature as close to 22 °C as possible.
|
||||
|
||||
The bang-bang controller does not use the set points this way. If you set the lower set point to 20 °C and set the
|
||||
upper set point to 22 °C, then *the temperature will be brought as high as 22 °C but go no lower than 20 °C.*
|
||||
|
||||
The behavior is not difficult to understand, but, as we've learned from many discussions on the Discord server, it
|
||||
departs from what most people seem to expect.
|
||||
|
||||
Which is Right for Me?
|
||||
**********************
|
||||
|
||||
It comes down to two points:
|
||||
|
||||
- If you have a dual-function system (both heating and cooling), you'll almost certainly want to use the
|
||||
:doc:`thermostat <thermostat>` component.
|
||||
- If you have a single-function system *and* have a specific need or desire to manually control both the upper and
|
||||
lower bounds for hysteresis, use the bang-bang controller.
|
||||
|
||||
In all other situations, the :doc:`thermostat <thermostat>` component is probably best.
|
||||
|
||||
See Also
|
||||
--------
|
||||
|
||||
|
@ -270,6 +270,11 @@ Advanced Options
|
||||
While this platform uses the term temperature everywhere, it can also be used to regulate other values.
|
||||
For example, controlling humidity is also possible with this platform.
|
||||
|
||||
Bang-bang vs. Thermostat
|
||||
------------------------
|
||||
|
||||
Please see the :doc:`Bang-bang <bang_bang>` component's documentation for a detailed comparison of these two components.
|
||||
|
||||