mirror of
https://github.com/esphome/esphome-docs.git
synced 2024-12-26 17:27:47 +01:00
Thermostat enhancements doc updates (#1339)
This commit is contained in:
parent
e30144ea39
commit
a5b045d222
@ -90,24 +90,29 @@ modes that Home Assistant offers.
|
||||
Controller Behavior and Hysteresis
|
||||
----------------------------------
|
||||
|
||||
In addition to the set points, a hysteresis value determines how far the temperature may vary from the set point value(s)
|
||||
before an :ref:`action <config-action>` (cooling, heating, etc.) is triggered. It defaults to 0.5 °C.
|
||||
In addition to the set points, hysteresis values determine how far the temperature may vary from the set point value(s)
|
||||
before an :ref:`action <config-action>` (cooling, heating, etc.) is triggered. They each default to 0.5 °C. They are:
|
||||
|
||||
- ``cool_deadband``: The minimum temperature differential (temperature above the set point) before **engaging** cooling
|
||||
- ``cool_overrun``: The minimum temperature differential (cooling beyond the set point) before **disengaging** cooling
|
||||
- ``heat_deadband``: The minimum temperature differential (temperature below the set point) before **engaging** heat
|
||||
- ``heat_overrun``: The minimum temperature differential (heating beyond the set point) before **disengaging** heat
|
||||
|
||||
A question that often surfaces about this component is, "What is the expected behavior?" Let's quickly discuss
|
||||
*exactly when* the configured actions are called by the controller.
|
||||
|
||||
Consider the low set point (the one that typically activates heating) for a moment, and assume it is set to a common room
|
||||
temperature of 21 °C. As mentioned above, the controller uses a default hysteresis value of 0.5 °C, so let's assume that
|
||||
value here, as well. The controller as implemented in this component will allow the temperature to drop as low as the set
|
||||
point's value (21 °C) *minus* the hysteresis value (0.5 °C), or 20.5 °C, before calling ``heat_action`` to activate heating.
|
||||
temperature of 22 °C. Let's assume ``heat_deadband`` is set to 0.4 °C while ``heat_overrun`` is set to 0.6 °C. In this case,
|
||||
the controller will allow the temperature to drop as low as the set point's value (22 °C) *minus* the ``heat_deadband``
|
||||
value (0.4 °C), or 21.6 °C, before calling ``heat_action`` to activate heating.
|
||||
|
||||
After heating has been activated, it will remain active until the observed temperature reaches the set point (21 °C) *plus*
|
||||
the hysteresis value (0.5 °C), or 21.5 °C. Once this temperature is reached, ``idle_action`` will be called to deactivate
|
||||
After heating has been activated, it will remain active until the observed temperature reaches the set point (22 °C) *plus*
|
||||
the ``heat_overrun`` value (0.6 °C), or 22.6 °C. Once this temperature is reached, ``idle_action`` will be called to deactivate
|
||||
heating.
|
||||
|
||||
The same behavior applies to the high set point, although the behavior is reversed in a sense; given an upper set point of
|
||||
22 °C, ``cool_action`` would be called at 22.5 °C and ``idle_action`` would not be called until the temperature is reduced
|
||||
to 21.5 °C.
|
||||
23 °C, ``cool_deadband`` set to 0.3 °C and ``cool_overrun`` set to 0.7 °C, ``cool_action`` would be called at 23.3 °C and
|
||||
``idle_action`` would not be called until the temperature is reduced to 22.3 °C.
|
||||
|
||||
Important Terminology
|
||||
---------------------
|
||||
@ -142,12 +147,12 @@ The thermostat controller uses the sensor to determine whether it should heat or
|
||||
Default Target Temperatures and Mode
|
||||
************************************
|
||||
|
||||
These temperatures are used when the device first starts up.
|
||||
These configuration items determine default values the thermostat controller should use when it starts.
|
||||
|
||||
- **default_mode** (*Optional*, climate mode): The default climate mode the controller should use if it
|
||||
is unable to restore it from memory. One of:
|
||||
|
||||
- ``off``
|
||||
- ``off`` (default)
|
||||
- ``heat_cool``
|
||||
- ``cool``
|
||||
- ``heat``
|
||||
@ -264,10 +269,10 @@ These should be used to control the fan only, if available.
|
||||
Advanced Options
|
||||
****************
|
||||
|
||||
- **hysteresis** (*Optional*, float): Defines how far the temperature may vary from the target values before
|
||||
an :ref:`action <config-action>` (cooling, heating, etc.) is triggered. Defaults to 0.5 °C.
|
||||
- **target_temperature_change_action** (*Optional*, :ref:`Action <config-action>`): The action to call when the
|
||||
thermostat's target temperature(s) is/are changed.
|
||||
**Set Point Options/Behavior**
|
||||
|
||||
- **set_point_minimum_differential** (*Optional*, float): For dual-point/dual-function systems, the minimum
|
||||
required temperature difference between the heat and cool set points.
|
||||
- **away_config** (*Optional*): Additionally specify target temperature range settings for away mode.
|
||||
Away mode can be used to have a second set of target temperatures (for example, while the user is
|
||||
away or sleeping/at night).
|
||||
@ -280,6 +285,32 @@ Advanced Options
|
||||
**If configured, at least one of** ``default_target_temperature_low`` **and** ``default_target_temperature_high``
|
||||
**must be specified in the away mode configuration.**
|
||||
|
||||
**Additional Actions/Behavior**
|
||||
|
||||
- **fan_only_cooling** (*Optional*, boolean): If set to ``true``, when in the ``fan_only_mode`` climate mode,
|
||||
the ``fan_only_action`` will only be called when the observed temperature exceeds the upper set point plus
|
||||
``cool_deadband``. When set to ``false`` (the default), ``fan_only_action`` is called immediately when
|
||||
``fan_only_mode`` is activated, regardless of the current temperature or set points.
|
||||
- **target_temperature_change_action** (*Optional*, :ref:`Action <config-action>`): The action to call when the
|
||||
thermostat's target temperature(s) is/are changed.
|
||||
|
||||
|
||||
**Hysteresis Values**
|
||||
|
||||
- **cool_deadband** (*Optional*, float): The minimum temperature differential (temperature above the set point)
|
||||
before calling the cooling :ref:`action <config-action>`. Defaults to 0.5 °C.
|
||||
- **cool_overrun** (*Optional*, float): The minimum temperature differential (cooling beyond the set point)
|
||||
before calling the idle :ref:`action <config-action>`. Defaults to 0.5 °C.
|
||||
- **heat_deadband** (*Optional*, float): The minimum temperature differential (temperature below the set point)
|
||||
before calling the heating :ref:`action <config-action>`. Defaults to 0.5 °C.
|
||||
- **heat_overrun** (*Optional*, float): The minimum temperature differential (heating beyond the set point)
|
||||
before calling the idle :ref:`action <config-action>`. Defaults to 0.5 °C.
|
||||
- **hysteresis** (*Optional*, float): This configuration option provides a one-line way to configure *all* "deadband"
|
||||
and "overrun" values identified above. Note that the above configuration options each take precedence over this
|
||||
value. *This option is deprecated and may be removed in a future release.*
|
||||
|
||||
|
||||
|
||||
.. note::
|
||||
|
||||
- While this platform uses the term temperature everywhere, it can also be used to regulate other values.
|
||||
|
Loading…
Reference in New Issue
Block a user