mirror of
https://github.com/esphome/esphome-docs.git
synced 2024-11-15 10:45:41 +01:00
84 lines
3.0 KiB
ReStructuredText
84 lines
3.0 KiB
ReStructuredText
CT Clamp Current Sensor
|
|
=======================
|
|
|
|
.. seo::
|
|
:description: Instructions for setting up ct clamp sensors.
|
|
:image: ct_clamp.jpg
|
|
|
|
The Current Transformer Clamp (``ct_clamp``) sensor allows you to hook up a CT Clamp to an analog
|
|
voltage sensor (like the :doc:`ADC sensor <adc>`) and convert the readings to measured single phase AC current.
|
|
|
|
First, you need to set up a voltage sensor source (:doc:`ADC sensor <adc>`, but for example also
|
|
:doc:`ADS1115 <ads1115>`) and pass it to the CT clamp sensor with the ``sensor`` option.
|
|
|
|
Please also see `this guide <https://learn.openenergymonitor.org/electricity-monitoring/ct-sensors/introduction>`__
|
|
as an introduction to the working principle of CT clamp sensors and how to hook them up to your device.
|
|
|
|
.. figure:: images/ct_clamp-ui.png
|
|
:align: center
|
|
:width: 80.0%
|
|
|
|
.. code-block:: yaml
|
|
|
|
# Example configuration entry
|
|
sensor:
|
|
- platform: ct_clamp
|
|
sensor: adc_sensor
|
|
name: "Measured Current"
|
|
update_interval: 60s
|
|
|
|
# Example source sensor
|
|
- platform: adc
|
|
pin: A0
|
|
id: adc_sensor
|
|
|
|
Configuration variables:
|
|
------------------------
|
|
|
|
- **name** (**Required**, string): The name of the sensor.
|
|
- **sensor** (**Required**, :ref:`config-id`): The source sensor to measure voltage values from.
|
|
- **sample_duration** (*Optional*, :ref:`config-time`): The time duration to sample the current clamp
|
|
with. Higher values can increase accuracy. Defaults to ``200ms`` which would be 10 whole cycles on a 50Hz system.
|
|
- **update_interval** (*Optional*, :ref:`config-time`): The interval
|
|
to check the sensor. Defaults to ``60s``. The **update_interval** for ``ct_clamp`` has to be greater than **sample_duration**.
|
|
- **id** (*Optional*, :ref:`config-id`): Manually specify the ID used for code generation.
|
|
- All other options from :ref:`Sensor <config-sensor>`.
|
|
|
|
Calibration
|
|
-----------
|
|
|
|
This sensor needs calibration to show correct values, for this you can use the
|
|
:ref:`calibrate_linear <sensor-filter-calibrate_linear>` sensor filter. First, hook up a known
|
|
current load like a lamp that uses a known amount of current.
|
|
|
|
Then switch it on and see what value the CT clamp sensor reports. For example in the configuration below
|
|
a 4.0 A device is showing a value of 0.1333 in the logs. Now go into your configuration file
|
|
|
|
.. code-block:: yaml
|
|
|
|
# Example configuration entry
|
|
sensor:
|
|
- platform: ct_clamp
|
|
sensor: adc_sensor
|
|
name: "Measured Current"
|
|
update_interval: 60s
|
|
filters:
|
|
- calibrate_linear:
|
|
# Measured value of 0 maps to 0A
|
|
- 0 -> 0
|
|
# Known load: 4.0A
|
|
# Value shown in logs: 0.1333A
|
|
- 0.1333 -> 4.0
|
|
|
|
Recompile and upload, now your CT clamp sensor is calibrated!
|
|
|
|
See Also
|
|
--------
|
|
|
|
- `EMonLib <https://github.com/openenergymonitor/EmonLib>`__
|
|
- `CT Clamp Guide <https://learn.openenergymonitor.org/electricity-monitoring/ct-sensors/introduction>`__
|
|
- :doc:`adc`
|
|
- :doc:`ads1115`
|
|
- :apiref:`sensor/ct_clamp_sensor.h`
|
|
- :ghedit:`Edit`
|