Bang Bang Climate Controller
|
|
============================
|
|
|
|
.. seo::
|
|
:description: Instructions for setting up Bang Bang climate controllers with ESPHome.
|
|
:image: air-conditioner.png
|
|
|
|
The ``bang_bang`` climate platform allows you to regulate a value with a
|
|
`bang-bang controller <https://en.wikipedia.org/wiki/Bang%E2%80%93bang_control>`__ (also called hysteresis controller).
|
|
|
|
.. note::
|
|
|
|
A number of people have asked about the behavior of the bang-bang controller. In version 1.15, a
|
|
:doc:`thermostat <thermostat>` component was added which behaves more like a common thermostat; it is
|
|
essentially two bang-bang controllers in one. Please see the `Bang-bang vs. Thermostat`_ section below
|
|
if you are not sure which is appropriate for your application.
|
|
|
|
The bang-bang controller's principle of operation is quite simple. First, you specify an observable
|
|
value (for example the temperature of a room). The controller will try to keep this observed value
|
|
in a defined range. To do this, the controller can activate objects like a heating unit to change
|
|
the observed value.
|
|
|
|
The range that the controller will try to keep the observed value in can be controlled through the
|
|
front-end with the ``target_temperature_low`` and ``target_temperature_high`` values (see screenshot below).
|
|
As soon as the observed temperature dips below or above this range it will activate one of the
|
|
defined actions ``cool_action``, ``heat_action`` and ``idle_action``.
|
|
|
|
There are three types of bang bang controllers this platform can represent:
|
|
|
|
- **Heaters**: For devices where the observed temperature can only be increased.
|
|
|
|
- As soon as the temperature goes below the lower target temperature, ``heat_action`` will be called.
|
|
- When the temperature goes above the higher temperature, ``idle_action`` will be called.
|
|
|
|
- **Coolers**: For devices where the observed temperature can only be decreased.
|
|
|
|
- As soon as the temperature goes above the higher target temperature, ``cool_action`` will be called.
|
|
- When the temperature goes below the lower temperature, ``idle_action`` will be called.
|
|
|
|
- **Heater+Cooler**: For devices where the temperature can both actively be increased and decreased.
|
|
|
|
- When the current temperature is below the lower target temperature, ``heat_action`` is called.
|
|
- When the current temperature is within the target temperature range, ``idle_action`` is called.
|
|
- When the current temperature is above the higher target temperature, ``cool_action`` is called.
|
|
|
|
Do note that the actions are only called when the current temperature leaves the target temperature range.
|
|
|
|
.. figure:: images/climate-ui.png
|
|
:align: center
|
|
:width: 60.0%
|
|
|
|
.. code-block:: yaml
|
|
|
|
# Example configuration entry
|
|
climate:
|
|
- platform: bang_bang
|
|
name: "Bang Bang Climate Controller"
|
|
sensor: my_temperature_sensor
|
|
default_target_temperature_low: 20 °C
|
|
default_target_temperature_high: 22 °C
|
|
|
|
heat_action:
|
|
- switch.turn_on: heater
|
|
idle_action:
|
|
- switch.turn_off: heater
|
|
|
|
Configuration variables
|
|
-----------------------
|
|
|
|
- **sensor** (**Required**, :ref:`config-id`): The sensor that is used to measure the current temperature.
|
|
- **default_target_temperature_low** (**Required**, float): The default low target temperature for
|
|
the control algorithm. This can be dynamically set in the frontend later.
|
|
- **default_target_temperature_high** (**Required**, float): The default high target temperature for
|
|
the control algorithm. This can be dynamically set in the frontend later.
|
|
- **idle_action** (**Required**, :ref:`Action <config-action>`): The action to call when
|
|
the climate device wants to enter idle mode.
|
|
- **heat_action** (*Optional*, :ref:`Action <config-action>`): The action to call when
|
|
the climate device wants to heating mode and increase the current temperature. At least one
|
|
of ``heat_action`` and ``cool_action`` need to be specified.
|
|
- **cool_action** (*Optional*, :ref:`Action <config-action>`): The action to call when
|
|
the climate device wants to cooling mode and decrease the current temperature.
|
|
- All other options from :ref:`Climate <config-climate>`.
|
|
|
|
Advanced options:
|
|
|
|
- **away_config** (*Optional*): Additionally specify target temperature range settings for away mode.
|
|
Away mode can be used to have a second set of target temperatures (for example while the user is
|
|
away or during nighttime)
|
|
|
|
- **default_target_temperature_low** (**Required**, float): The default low target temperature for
|
|
the control algorithm during away mode.
|
|
- **default_target_temperature_high** (**Required**, float): The default high target temperature for
|
|
the control algorithm during away mode.
|
|
|
|
.. note::
|
|
|
|
While this platform uses the term temperature everywhere, it can also be used for other values.
|
|
For example, controlling humidity is also possible with this platform.
|
|
|
|
Bang-bang vs. Thermostat
|
|
------------------------
|
|
|
|
The behavior of the bang-bang controller is a topic that has surfaced on the ESPHome Discord server
|
|
countless times -- many people have been confused by what it does. While they are similar, there are
|
|
two key differences between the bang-bang component and the :doc:`thermostat <thermostat>` component:
|
|
|
|
- When actions are triggered
|
|
- How the set points are used by the controller
|
|
|
|
Now is a good time to ensure you understand exactly how a bang-bang controller should behave; if you do not have
|
|
a clear understanding of this, be sure to check out the
|
|
`Wikipedia article <https://en.wikipedia.org/wiki/Bang%E2%80%93bang_control>`__.
|
|
|
|
The Problem with Dual-Function Systems
|
|
**************************************
|
|
|
|
If you are not attempting to operate a system that can both heat and cool, you'll likely want to skip to the next
|
|
section about user interface.
|
|
|
|
As outlined above, in general:
|
|
|
|
- As soon as the temperature goes below the *lower* target temperature, ``heat_action`` is called to activate heating.
|
|
- Heating will continue until the temperature reaches the *upper* target temperature, at which point ``idle_action`` is called to stop heating.
|
|
- As soon as the temperature goes above the *upper* target temperature, ``cool_action`` is called to activate cooling.
|
|
- Cooling will continue until the temperature reaches the *lower* target temperature, at which point ``idle_action`` is called to stop cooling.
|
|
|
|
A single bang-bang controller may work well for systems that only heat or only cool; however, it begins to break down
|
|
when applied to systems that may both heat *and* cool. This is simply because both actions are tied to both set
|
|
points -- that is, the point at which heating stops *is also the point at which cooling begins*. The reverse is also
|
|
true: the point at which cooling stops *is also the point at which heating begins*. Let's look at an example:
|
|
|
|
Consider a system that both heats and cools. The ``target_temperature_low`` set point is 20 °C while the
|
|
``target_temperature_high`` set point is 22 °C. The sensor reports that the temperature is 19.75 °C, so the controller
|
|
calls ``heat_action`` to activate heating. Heating continues until the temperature reaches ``target_temperature_high``
|
|
(22 °C in this case). Once this temperature is achieved, ``idle_action`` is called to stop heating. *However*, should
|
|
temperature drift even slightly above ``target_temperature_high``--even just a fraction of a degree for a fraction of
|
|
a second--the controller will call ``cool_action`` to begin cooling. Now, cooling will continue until
|
|
``target_temperature_low`` is reached again, but, as before, should the temperature drift even slightly below
|
|
``target_temperature_low`` for even a fraction of a second, ``heat_action`` will be invoked again, and the cycle will
|
|
repeat. It will "ping-pong" between the two set points, potentially forever. Oscillation at the "edges" of the
|
|
hysteresis window, or going past the set point in either direction, should be expected; consider, for example, a heater
|
|
that is turned off after it reaches its set point. The heating element will remain hot (potentially for quite a while),
|
|
and as such will continue to heat the air until the element fully cools down to match the ambient air/room temperature.
|
|
|
|
The :doc:`thermostat <thermostat>` component differs in that there is hysteresis around *each* set point. For example,
|
|
if the ``target_temperature_low`` set point is 20 °C, and the (default) hysteresis value of 0.5 °C is used,
|
|
``heat_action`` is called at a temperature of 19.5 °C and ``idle_action`` is called at 20.5 °C. If cooling, as defined
|
|
by ``target_temperature_high``, is set to 22 °C, ``cool_action`` would be called at 22.5 °C and ``idle_action`` called
|
|
at 21.5 °C. Again, it is essentially two bang-bang controllers in one.
|
|
|
|
Behavioral differences aside, there is another important difference between these two components: user interface.
|
|
|
|
User Interface
|
|
**************
|
|
|
|
The interaction with this component via the Home Assistant user interface is also different than what is seen on most
|
|
common residential thermostats. Generally speaking, most thermostats allow either one or two set points -- one of them
|
|
is associated with heating while the other with cooling, and this is exactly how the :doc:`thermostat <thermostat>`
|
|
component uses them. If you set the "heat" set point to 20 °C, most people assume this means the heating system will
|
|
keep the temperature as close to 20 °C as possible. The same is true for the upper set point, for cooling: if you set
|
|
a temperature of 22 °C, most people assume the cooling system will keep the temperature as close to 22 °C as possible.
|
|
|
|
The bang-bang controller does not use the set points this way. If you set the lower set point to 20 °C and set the
|
|
upper set point to 22 °C, then *the temperature will be brought as high as 22 °C but go no lower than 20 °C.*
|
|
|
|
The behavior is not difficult to understand, but, as we've learned from many discussions on the Discord server, it
|
|
departs from what most people seem to expect.
|
|
|
|
Which is Right for Me?
|
|
**********************
|
|
|
|
It comes down to two points:
|
|
|
|
- If you have a dual-function system (both heating and cooling), you'll almost certainly want to use the
|
|
:doc:`thermostat <thermostat>` component.
|
|
- If you have a single-function system *and* have a specific need or desire to manually control both the upper and
|
|
lower bounds for hysteresis, use the bang-bang controller.
|
|
|
|
In all other situations, the :doc:`thermostat <thermostat>` component is probably best.
|
|
|
|
See Also
|
|
--------
|
|
|
|
- :doc:`/components/climate/index`
|
|
- :apiref:`bang_bang/bang_bang_climate.h`
|
|
- :ghedit:`Edit`
|