mirror of
https://github.com/esphome/esphome-docs.git
synced 2024-11-10 10:11:29 +01:00
0b041128a6
* fix enum docs style * schema fixes updates for 2023.2 * support multi key prop * format fixes * Format fixes * set typed * fix code quotes * add platforms --------- Co-authored-by: H. Árkosi Róbert <robreg@zsurob.hu>
442 lines
18 KiB
ReStructuredText
442 lines
18 KiB
ReStructuredText
PID Climate
|
|
===========
|
|
|
|
.. seo::
|
|
:description: Instructions for setting up PID climate controllers with ESPHome.
|
|
:image: function.svg
|
|
|
|
The ``pid`` climate platform allows you to regulate a value with a
|
|
`PID controller <https://en.wikipedia.org/wiki/PID_controller>`__.
|
|
|
|
PID controllers are good at modulating an output signal to get a sensor reading to a specified
|
|
setpoint. For example, it can be used to modulate the power of a heating unit to get the
|
|
temperature to a user-specified setpoint.
|
|
|
|
.. note::
|
|
|
|
PID is like cruise control in the cars: it keeps the car's speed constant by continuously
|
|
adjusting the fuel quantity, based on load measurements. Eg when the car has to go up on a hill,
|
|
the system notices the load increase thus immediately gives more fuel to the engine; and when it
|
|
goes down on the other side of the hill, it notices the load decrease thus reduces or cuts off fuel
|
|
completely so that car speed remains as constant as possible. The calculation takes in consideration
|
|
constants like car weight, wind resistance etc.
|
|
|
|
This kind of math can be used for a heating or cooling system too, and an auto-tuning algorithm can help
|
|
determining such constants, which mainly describe the heat loss of the room or building. Goal is to
|
|
keep the temperature as constant as possible, and smooth out oscillations otherwise produced by
|
|
classic thermostats.
|
|
|
|
Explaining how PID controllers work in detail is out of scope of this documentation entry,
|
|
but there's a nice article explaining the function principle `here <https://blog.opticontrols.com/archives/344>`__.
|
|
|
|
.. code-block:: yaml
|
|
|
|
# Example configuration entry
|
|
climate:
|
|
- platform: pid
|
|
name: "PID Climate Controller"
|
|
sensor: temperature_sensor
|
|
default_target_temperature: 21°C
|
|
heat_output: heater
|
|
control_parameters:
|
|
kp: 0.49460
|
|
ki: 0.00487
|
|
kd: 12.56301
|
|
output_averaging_samples: 5 # smooth the output over 5 samples
|
|
derivative_averaging_samples: 5 # smooth the derivative value over 10 samples
|
|
deadband_parameters:
|
|
threshold_high: 0.5°C # deadband within +/-0.5°C of target_temperature
|
|
threshold_low: -0.5°C
|
|
|
|
Configuration variables:
|
|
------------------------
|
|
|
|
- **sensor** (**Required**, :ref:`config-id`): The sensor that is used to measure the current
|
|
temperature.
|
|
- **default_target_temperature** (**Required**, float): The default target temperature (setpoint)
|
|
for the control algorithm. This can be dynamically set in the frontend later.
|
|
- **heat_output** (*Optional*, :ref:`config-id`): The ID of a :ref:`float output <config-output>`
|
|
that increases the current temperature. At least one of ``heat_output`` and ``cool_output`` must
|
|
be specified.
|
|
- **cool_output** (*Optional*, :ref:`config-id`): The ID of a :ref:`float output <config-output>`
|
|
that decreases the current temperature. At least one of ``heat_output`` and ``cool_output`` must
|
|
be specified.
|
|
- **control_parameters** (**Required**): Control parameters of the PID controller.
|
|
|
|
- **kp** (**Required**, float): The factor for the proportional term of the PID controller.
|
|
- **ki** (*Optional*, float): The factor for the integral term of the PID controller.
|
|
Defaults to ``0``.
|
|
- **kd** (*Optional*, float): The factor for the derivative term of the PID controller.
|
|
Defaults to ``0``.
|
|
- **min_integral** (*Optional*, float): The maximum value of the integral term multiplied by
|
|
``ki`` to prevent windup. Defaults to ``-1``.
|
|
- **max_integral** (*Optional*, float): The minimum value of the integral term multiplied by
|
|
``ki`` to prevent windup. Defaults to ``1``.
|
|
- **starting_integral_term** (*Optional*, float): Set the initial output, by priming the integral
|
|
term. This is useful for when your system is rebooted and you don't want to wait
|
|
for it to get back equilibrium.
|
|
|
|
- **output_averaging_samples** (*Optional*, int): average the output over this many samples. PID controllers
|
|
can be quite sensitive to small changes on the input sensor. By averaging the last X output samples,
|
|
the temperature can be more stable. However, the larger the sampling window, the less responsive the
|
|
PID controller. Defaults to ``1`` which is no sampling/averaging.
|
|
|
|
- **derivative_averaging_samples** (*Optional*, int): average the derivative term over this many samples. Many
|
|
controllers don't use the derivative term because it is sensitive to slight changes in the input sensor.
|
|
By taking an average of the derivative term it might become more useful for you. Most PID controllers call
|
|
this derivative filtering. The derivative term is used to pre-act so don't filter too much. Defaults to ``1``
|
|
which is no sampling/averaging.
|
|
|
|
- **deadband_parameters** (*Optional*): Enables a deadband to stabilise and minimise changes in the
|
|
output when the temperature is close to the target temperature. See `Deadband Setup`_.
|
|
|
|
- **threshold_high/threshold_low** (**Required**, float): Specifies a high/low
|
|
threshold defining the deadband around the target temperature. For instance with
|
|
``default_target_temperature`` of ``21°C`` and thresholds of ``+/-0.5°C``, the deadband will be
|
|
between ``20.5°C - 21.5°C``. The PID controller will limit output changes within the deadband.
|
|
- **kp_multiplier** (*Optional*, float): Set the ``kp`` gain when inside the deadband. Defaults to ``0``.
|
|
- **ki_multiplier** (*Optional*, float): Set the ``ki`` gain when inside the deadband. Defaults to ``0``.
|
|
- **kd_multiplier** (*Optional*, float): Set the ``kd`` gain when inside the deadband. Recommended this
|
|
is set to ``0``. Defaults to ``0``.
|
|
|
|
- **deadband_output_averaging_samples** (*Optional*, int): Typically when inside the deadband the PID Controller has
|
|
reached a state of equilibrium, so it advantageous to use a higher number of output samples
|
|
like 10-30 samples. Defaults to ``1`` which is no sampling/averaging.
|
|
|
|
- All other options from :ref:`Climate <config-climate>`.
|
|
|
|
.. _pid-setup:
|
|
|
|
PID Controller Setup
|
|
--------------------
|
|
|
|
To set up a PID climate controller, you need a couple of components:
|
|
|
|
- A :ref:`Sensor <config-sensor>` to read the current temperature (``sensor``).
|
|
- At least one :ref:`float output <config-output>` to drive for heating or cooling (or both).
|
|
This could for example be a PWM output via :doc:`/components/output/sigma_delta_output` or :doc:`/components/output/slow_pwm` that drives a heating unit.
|
|
|
|
Please note the output *must* be controllable with continuous value (not only ON/OFF, but any state
|
|
in between for example 50% heating power).
|
|
|
|
.. note::
|
|
|
|
The sensor should have a short update interval. The PID update frequency is tied to the update
|
|
interval of the sensor. Set a short ``update_interval`` like ``5s`` on the sensor.
|
|
|
|
We recommend putting a filter on the sensor (see filters in :doc:`/components/sensor/index`) and
|
|
using ``output_averaging_samples`` to calm the PID sensor from a noisy input sensor.
|
|
|
|
Deadband Setup
|
|
--------------
|
|
A deadband is used to prevent the PID controller from further adjusting the power
|
|
once the temperature has settled within a range of the target temperature.
|
|
|
|
We do this by specifying a high/low threshold of the target temperature.
|
|
|
|
To understand the benefit, consider a heating/cooling HVAC which is constantly
|
|
oscillating between heating and cooling as the thermostat records very minor
|
|
changes from +0.1º to -0.1º. Clearly this is undesirable and will cause wear
|
|
and tear as the HVAC oscillates. With a deadband in place the heater won't
|
|
activate until the thermostat breaches the low_threshold and the cooler won't activate
|
|
until the thermostat breaches the high_threshold.
|
|
|
|
The most basic setup specifies the threshold around the target temperature as follows:
|
|
|
|
.. code-block:: yaml
|
|
|
|
default_target_temperature: 21°C
|
|
...
|
|
deadband_parameters:
|
|
threshold_high: 0.5°C
|
|
threshold_low: -1.0°C
|
|
|
|
In this example the deadband is between ``20.0°C - 21.5°C``. The PID controller will limit any output
|
|
variation inside this deadband. How it limits depends on how you set the `Deadband Multipliers`_.
|
|
|
|
.. figure:: images/deadband1.png
|
|
|
|
Deadband Multipliers
|
|
********************
|
|
|
|
Deadband Multipliers tell the controller how to operate when inside of the deadband.
|
|
|
|
Each of the p,i and d terms can be controlled using the kp, ki and kd multipliers. For instance, if the kp_multiplier
|
|
is set to 0.05 then the final proportional term will be set to 5% of its normal value within the deadband.
|
|
|
|
If all of the multipliers are set to 0, then the controller will not adjust power at all within the
|
|
deadband. This is the default behavior.
|
|
|
|
Most deadband implementations set kp and ki multipliers to a small gain like ``0.05`` and set
|
|
derivative to 0. This means that the PID output will calmly make minor adjustments over a 20x longer
|
|
timeframe to stay within the deadband zone.
|
|
|
|
To start with we recommend just setting the ``ki_multiplier`` to ``0.05`` (5%). Then
|
|
set ``kp_multiplier`` to ``0.05`` (5%) if the controller is falling out of the deadband too often.
|
|
|
|
.. code-block:: yaml
|
|
|
|
default_target_temperature: 21°C
|
|
...
|
|
deadband_parameters:
|
|
threshold_high: 0.5°C
|
|
threshold_low: -1.0°C
|
|
kp_multiplier: 0.0 # proportional gain turned off inside deadband
|
|
ki_multiplier: 0.05 # integral accumulates at only 5% of normal ki
|
|
kd_multiplier: 0.0 # derviative is turned off inside deadband
|
|
deadband_output_averaging_samples: 15 # average the output over 15 samples within the deadband
|
|
|
|
.. figure:: images/deadband2.png
|
|
|
|
Deadband Output Averaging Samples
|
|
*********************************
|
|
Since we expect the PID Controller to be at equilibrium while inside the deadband, we can
|
|
average the output over a longer range of samples, like 15 samples. This helps even further
|
|
with temperature and controller stability.
|
|
|
|
.. _pid-autotune:
|
|
|
|
Autotuning
|
|
----------
|
|
|
|
Finding suitable ``kp``, ``ki`` and ``kd`` control parameters for the PID controller manually
|
|
needs some experience with PID controllers. ESPHome has an auto-tuning algorithm that automatically
|
|
finds suitable PID parameters to start using an adaption of the Ziegler-Nichols method with
|
|
relay autotuning (Åström and Hägglund).
|
|
|
|
To autotune the control parameters:
|
|
|
|
1. Set up the PID controller with all control parameters set to zero:
|
|
|
|
.. code-block:: yaml
|
|
|
|
climate:
|
|
- platform: pid
|
|
id: pid_climate
|
|
name: "PID Climate Controller"
|
|
sensor: temperature_sensor
|
|
default_target_temperature: 21°C
|
|
heat_output: heater
|
|
control_parameters:
|
|
kp: 0.0
|
|
ki: 0.0
|
|
kd: 0.0
|
|
|
|
2. Create a :doc:`template button </components/button/template>` to start autotuning later:
|
|
|
|
.. code-block:: yaml
|
|
|
|
button:
|
|
- platform: template
|
|
name: "PID Climate Autotune"
|
|
on_press:
|
|
- climate.pid.autotune: pid_climate
|
|
|
|
3. Compile & Upload the new firmware.
|
|
|
|
Now you should have a climate entity called *PID Climate Controller* and a button called
|
|
*PID Climate Autotune* visible in your frontend of choice.
|
|
|
|
The autotune algorithm works by repeatedly switching the heat/cool output to full power and off.
|
|
This induces an oscillation of the observed temperature and the measured period and amplitude
|
|
is automatically calculated. To do this, it needs to observe at least 3 oscillation cycles.
|
|
|
|
.. note::
|
|
|
|
You **have to set the setpoint** of the climate controller to a value the
|
|
device can reach. For example if the temperature of a room is to be controlled, the setpoint needs
|
|
to be above the ambient temperature. If the ambient temperature is 20°C, the setpoint of the
|
|
climate device should be set to at least ~24°C so that an oscillation can be induced.
|
|
|
|
Also take care of external influences, like for example when room temperature is severely affected by
|
|
outdoor weather like sun, if it starts to warm up the room in parallel with the heating
|
|
autotune will likely fail or give false results.
|
|
|
|
4. Set an appropriate setpoint (see note above) and turn on the climate controller (Heat, Cool or Auto).
|
|
|
|
5. Click the *PID Climate Autotune* button and look at the the logs of the device.
|
|
|
|
You should see output like
|
|
|
|
.. code-block:: text
|
|
|
|
PID Autotune:
|
|
Autotune is still running!
|
|
Status: Trying to reach 24.25 °C
|
|
Stats so far:
|
|
Phases: 4
|
|
Detected 5 zero-crossings
|
|
# ...
|
|
|
|
.. note::
|
|
|
|
In the output above, the autotuner is driving the heating output at 100% and trying to reach 24.25 °C.
|
|
|
|
This will continue for some time until data for 3 phases (6 crossings of the setpoint; or a bit more, depending on
|
|
the data quality) have been acquired.
|
|
|
|
The autotune algorithm may take a long time to complete, it depends on the time needed to reproduce the
|
|
heating up and cooling down oscillations the required number of times.
|
|
|
|
6. When the PID autotuner has succeeded, output like the one below can be seen:
|
|
|
|
.. code-block:: text
|
|
|
|
PID Autotune:
|
|
State: Succeeded!
|
|
All checks passed!
|
|
Calculated PID parameters ("Ziegler-Nichols PID" rule):
|
|
|
|
control_parameters:
|
|
kp: 0.49460
|
|
ki: 0.00487
|
|
kd: 12.56301
|
|
|
|
Please copy these values into your YAML configuration! They will reset on the next reboot.
|
|
|
|
As soon as the the autotune procedure finishes, the climate starts to work with the calculated parameters
|
|
so that expected operation can be immediately verified.
|
|
|
|
If satisfied, copy the values in ``control_parameters`` into your configuration:
|
|
|
|
.. code-block:: yaml
|
|
|
|
climate:
|
|
- platform: pid
|
|
# ...
|
|
control_parameters:
|
|
kp: 0.49460
|
|
ki: 0.00487
|
|
kd: 12.56301
|
|
|
|
The *PID Climate Autotune* button can be removed from the config, if the results are satisfactory,
|
|
it's not needed anymore.
|
|
|
|
7. Complete, compile & upload the updated firmware.
|
|
|
|
If the calculated PID parameters are not good, you can try some of the alternative parameters
|
|
printed below the main control parameters in the log output.
|
|
|
|
|
|
``climate.pid.autotune`` Action
|
|
-------------------------------
|
|
|
|
This action starts the autotune process of the PID controller.
|
|
|
|
.. code-block:: yaml
|
|
|
|
on_...:
|
|
# Basic
|
|
- climate.pid.autotune: pid_climate
|
|
|
|
# Advanced
|
|
- climate.pid.autotune:
|
|
id: pid_climate
|
|
noiseband: 0.25
|
|
positive_output: 25%
|
|
negative_output: -25%
|
|
|
|
Configuration variables:
|
|
|
|
- **id** (**Required**, :ref:`config-id`): ID of the PID Climate to start autotuning for.
|
|
- **noiseband** (*Optional*, float): The noiseband of the process (=sensor) variable. The value
|
|
of the PID controller must be able to reach this value. Defaults to ``0.25``.
|
|
- **positive_output** (*Optional*, float): The positive output power to drive the heat output at.
|
|
Defaults to ``1.0``.
|
|
- **negative_output** (*Optional*, float): The negative output power to drive the cool output at.
|
|
Defaults to ``-1.0``.
|
|
|
|
The ``positive_output`` and ``negative_output`` parameters can be used to compensate the heating or the
|
|
cooling process during the autotune, in the cases when they are not changing the temperature at the
|
|
same rate, resulting in a not symmetrical oscillation. The autotune result will print a message when
|
|
it's recommended to repeat the entire procedure with such parameters configured.
|
|
|
|
``climate.pid.set_control_parameters`` Action
|
|
---------------------------------------------
|
|
|
|
This action sets new values for the control parameters of the PID controller. This can be
|
|
used to manually tune the PID controller. Make sure to take update the values you want on
|
|
the YAML file! They will reset on the next reboot.
|
|
|
|
.. code-block:: yaml
|
|
|
|
on_...:
|
|
- climate.pid.set_control_parameters:
|
|
id: pid_climate
|
|
kp: 0.0
|
|
ki: 0.0
|
|
kd: 0.0
|
|
|
|
Configuration variables:
|
|
|
|
- **id** (**Required**, :ref:`config-id`): ID of the PID Climate to start autotuning for.
|
|
- **kp** (**Required**, float): The factor for the proportional term of the PID controller.
|
|
- **ki** (*Optional*, float): The factor for the integral term of the PID controller.
|
|
Defaults to ``0``.
|
|
- **kd** (*Optional*, float): The factor for the derivative term of the PID controller.
|
|
Defaults to ``0``.
|
|
|
|
``climate.pid.reset_integral_term`` Action
|
|
------------------------------------------
|
|
|
|
This action resets the integral term of the PID controller to 0. This might be necessary under certain
|
|
conditions to avoid the control loop to overshoot (or undershoot) a target.
|
|
|
|
.. code-block:: yaml
|
|
|
|
on_...:
|
|
# Basic
|
|
- climate.pid.reset_integral_term: pid_climate
|
|
|
|
Configuration variables:
|
|
|
|
- **id** (**Required**, :ref:`config-id`): ID of the PID Climate being reset.
|
|
|
|
``pid`` Sensor
|
|
--------------
|
|
|
|
Additionally, the PID climate platform provides an optional sensor platform to monitor
|
|
the calculated PID parameters to help finding good PID values.
|
|
|
|
.. code-block:: yaml
|
|
|
|
sensor:
|
|
- platform: pid
|
|
name: "PID Climate Result"
|
|
type: RESULT
|
|
|
|
Configuration variables:
|
|
|
|
- **name** (**Required**, string): The name of the sensor
|
|
- **type** (**Required**, string): The value to monitor. One of
|
|
|
|
- ``RESULT`` - The resulting value (sum of P, I, and D terms).
|
|
- ``ERROR`` - The calculated error (setpoint - process_variable)
|
|
- ``PROPORTIONAL`` - The proportional term of the PID controller.
|
|
- ``INTEGRAL`` - The integral term of the PID controller.
|
|
- ``DERIVATIVE`` - The derivative term of the PID controller.
|
|
- ``HEAT`` - The resulting heating power to the supplied to the ``heat_output``.
|
|
- ``COOL`` - The resulting cooling power to the supplied to the ``cool_output``.
|
|
- ``KP`` - The current factor for the proportional term of the PID controller.
|
|
- ``KI`` - The current factor for the integral term of the PID controller.
|
|
- ``KD`` - The current factor for the differential term of the PID controller.
|
|
|
|
Advanced options:
|
|
|
|
- **climate_id** (*Optional*, :ref:`config-id`): The ID of the pid climate to get the values from.
|
|
|
|
See Also
|
|
--------
|
|
|
|
- Ziegler-Nichols Method: Nichols, N. B. and J. G. Ziegler (1942), 'Optimum settings for automatic
|
|
controllers', Transactions of the ASME, 64, 759-768
|
|
- Åström, K. J. and T. Hägglund (1984a), 'Automatic tuning of simple regulators',
|
|
Proceedings of IFAC 9th World Congress, Budapest, 1867-1872
|
|
- :doc:`/components/climate/index`
|
|
- :doc:`/components/output/sigma_delta_output`
|
|
- :doc:`/components/output/slow_pwm`
|
|
- `Principles of PID <https://blog.opticontrols.com/archives/344>`__
|
|
- :apiref:`pid/pid_climate.h`
|
|
- :apiref:`PID Autotuner <pid/pid_autotuner.h>`
|
|
- :ghedit:`Edit`
|